LEO TECHNICAL ACADEMY · MODULE 5

⚡ RED RISK LESSON

Electrical Safety Awareness — Mandatory Pre-Entry Acknowledgment
⚠ This Lesson Is Classified RED

Electrical hazards are the #3 cause of industrial worker fatalities in the United States (OSHA). Electrocution accounts for approximately 400 worker deaths per year.

Violation of electrical safety rules at LEO Industrial Services results in immediate removal from electrical work assignments.

In this lesson you will NOT perform any electrical work. You will learn the rules that govern when and how electrical work can be approached, who is authorized to perform it, and what to do when you encounter an unexpected electrical hazard.
Current as low as 10 mA can cause loss of muscle control. At 100–200 mA, ventricular fibrillation occurs. Normal household current at wet-skin resistance can deliver a potentially lethal 120 mA.

Required PPE Acknowledgment — Check All Before Proceeding

⚠ LEO Ops Portal — Development Draft — Not Approved for Employee Use
Module 5 — Electrical Systems
Lesson 5.1 — Electrical Safety Awareness
L1 — Awareness 🔴 Red Risk ⚡ Electrical ⏱ 55 min LEO-ACE-05-001 v1.0 · 2026-06-14

In This Lesson

§01 Why Electricity Kills §02 Objectives §03 Prerequisites §04 LEO Work Rule §05 LOTO §06 Arc Flash §07 Electrical PPE §08 Test Before Touch §09 Hazards §10 Emergency Response §11 Hazard Quiz §12 OSHA Reference §13 Assessment §14 Field Checklist
§01

Why Electricity Kills

⚡ Critical Fact
Current — not voltage — is the primary determinant of injury severity. Voltage matters only because it drives current through resistance. A high-voltage source with sufficient resistance can produce survivable current. A low-voltage source across wet skin can produce lethal current.

Current Thresholds and Physiological Effects

Current (AC)Effect on Human BodyRisk Level
1 mABarely perceptible tingleLow
5 mASlight shock — generally not harmfulLow
6–16 mA"Let-go" threshold — muscle contraction begins; may be unable to release gripModerate
17–99 mAPainful shock; respiratory difficulty; severe muscle contractionsHigh
100–200 mAVentricular fibrillation — typically fatal without immediate defibrillationFATAL
>200 mASevere burns, cardiac arrest, tissue destruction; paradoxically may be "shocked out" of VFEXTREME

Ohm's Law Applied to the Human Body

The human body is an electrical conductor with variable resistance. Skin resistance dominates: dry skin ≈ 100,000 Ω, wet skin ≈ 1,000 Ω. Internal body resistance (tissue, blood) is approximately 300–500 Ω.

Calculation — Wet Skin at 120V
I = V ÷ R = 120V ÷ 1,000Ω = 120 mA

120 mA is well within the ventricular fibrillation range. Household 120V is potentially lethal under wet conditions.

Calculation — Wet Skin at 480V
I = V ÷ R = 480V ÷ 1,000Ω = 480 mA

480 mA causes immediate cardiac arrest and severe burns. 480V three-phase is the most common lethal voltage in industrial settings.

Contact Types

Contact TypeDescriptionCommon Scenario
Series (hand-to-hand)Current enters one hand, travels across the chest/heart, exits the other hand. Crosses the heart — most dangerous path.Grabbing both sides of a live conductor
Series (hand-to-foot)Current enters hand, travels down through torso and legs to ground. Also crosses the heart.Standing on a grounded surface while touching an energized part
ParallelTouching an energized conductor while you yourself are grounded — you become a path to ground.Most common industrial shock scenario

The 4 Electrical Hazards

HazardMechanismOutcome
ShockCurrent through the body via direct contact with energized conductorBurns, cardiac arrest, respiratory failure, death
Arc FlashSudden release of electrical energy through ionized air — temperatures up to 35,000°FBurns (1.2 cal/cm² causes second-degree burn), blindness, death
Arc BlastRapid expansion of vaporized copper and superheated air — pressure waves exceeding 2,000 lbs/ft²Barotrauma, shrapnel injuries, death. Molten copper travels >700 mph.
FireElectrical arc ignites surrounding materials; overloaded conductors overheat insulationBurns, smoke inhalation, facility damage

Voltage Danger Levels

✓ De-energized
Safe to work (after LOTO + verify)
⚠ 50–120V
CAUTION — wet skin lethal
⛔ 120–480V
DANGER — arc flash risk
☠ 480V+
EXTREME — immediate death risk
§02

Learning Objectives

Upon completing this lesson, you will be able to:

§03

Prerequisites

RequirementCodeStatus
Lockout/Tagout FundamentalsLEO-LOTO-001REQUIRED — must be completed first
Module 2 Safety TrainingLEO-ACE-02REQUIRED
Hazard Symbol LiteracyLEO-ACE-01-003Recommended
⚠ Prerequisite Enforcement
Technicians who have not completed LEO-LOTO-001 should not continue this lesson. LOTO procedures are referenced throughout and assumed as foundational knowledge.
§04

The LEO Electrical Work Rule

⚡ LEO Electrical Work Rule

"Only Qualified Electrical Personnel (QEP) may work on or near exposed energized conductors above 50V."

Definition of Qualified Electrical Personnel (QEP)

A LEO team member is designated QEP only if they meet all three of the following criteria:

CriterionRequirement
Training currencyHas completed NFPA 70E training within the last 3 years
Licensure or designationHolds a valid Journeyman or Master Electrician license, OR has been formally designated QEP by LEO management in writing
Arc flash PPE trainingHas completed arc flash PPE training and is familiar with CAT 0–4 PPE requirements

Non-QEP Roles — What You MAY Do

✓ Permitted for Non-QEP (L1/L2 Technicians, Field Operators)

Non-QEP Roles — What You Must NEVER Do

⛔ Prohibited for Non-QEP — Zero Exceptions

Correct Response to Unexpected Electrical Hazard

⚠ If You Discover an Unexpected Electrical Hazard
  1. Stop all work in the area immediately
  2. Do not attempt to close, cover, or handle the hazard yourself
  3. Barricade the area to prevent others from entering
  4. Contact your LEO supervisor and request QEP response
  5. Document the hazard (photo if safe to do so from a distance)
§05

OSHA 1910.147 — LOTO for Electrical Energy

Lockout/Tagout for electrical energy has specific requirements beyond mechanical LOTO. Electrical systems may have multiple energy sources, stored energy in capacitors, and the ability to be backfed from secondary sources. Never assume a circuit is de-energized because a breaker is open.

⚡ Critical Warning
Breakers can be backfed. Circuits can be cross-connected. Capacitors can hold charge for minutes after de-energization. The only safe circuit is a verified circuit.

8-Step Electrical LOTO Procedure

1
Identify All Energy Sources

Review the single-line diagram (SLD) for the equipment. Industrial equipment commonly has multiple feeds — primary, control power, UPS backup, and generator circuits. All sources must be identified before any isolation begins. Never assume a single-feed topology.

2
Notify Affected Employees

Inform all workers in the area that electrical LOTO is being applied. This prevents personnel from inadvertently energizing equipment from a remote location or another panel.

3
De-Energize — Open Main Disconnect / Breaker

Turn the equipment off using its normal stopping procedure first. Then open the main disconnect switch, circuit breaker, or motor controller. Use QEP or trained personnel for this step at voltages above 50V.

4
Isolate — Physically Disconnect the Energy Source

Open the disconnect switch to visible-gap isolation, pull fuses from the fuse block, rack out the breaker to the disconnected position, or open the knife switch. A breaker in the OFF position is not isolation — the bus may still be energized.

5
Apply Lockout Device + Personal Lock

Attach a lockout hasp to the isolation point and apply your personal padlock. Your lock stays on until you remove it — no supervisor or manager may remove it without following the emergency removal procedure. Apply a DANGER tag with your name, date, and contact information.

6
Release Stored Electrical Energy

Discharge capacitors per manufacturer procedure (often 5–15 minutes of wait time, or active discharge with a resistor). Bleed down UPS systems. Discharge VFD (variable frequency drive) bus capacitors — many VFDs carry 480–800V DC on the bus for minutes after shutdown. Verify motor windings are not acting as generators (coast-down).

7
VERIFY Zero Energy — Test-Test-Test Sequence

Using a calibrated, appropriate-voltage-rated meter or non-contact voltage tester:
(a) Test the meter on a known live source to confirm the meter is functioning.
(b) Test the isolated circuit/terminals to verify zero voltage.
(c) Test the known live source again to confirm the meter did not fail during testing.
All three tests must pass. This is the test-test-test protocol. Skipping any step is a procedural violation.

8
Restore to Service

When work is complete: verify all tools, materials, and personnel are clear. Remove locks in reverse order of application. Notify affected employees. Restore energy in controlled sequence. Document LOTO removal.

⚠ Electrical-Specific LOTO Hazards Not Present in Mechanical LOTO
§06

Arc Flash Fundamentals

What Is an Arc Flash?

An arc flash is a sudden, uncontrolled release of electrical energy through ionized air when the voltage exceeds the dielectric strength of the air gap between conductors. The energy released in milliseconds can be catastrophic:

Arc Flash EffectMagnitudeConsequence
TemperatureUp to 35,000°F (4× the surface temperature of the sun)Instantaneous severe burns; ignition of all combustibles in the area
Pressure wave (Arc Blast)Can exceed 2,000 lbs/ft²Ruptures eardrums, throws workers, causes blunt trauma
ShrapnelMolten copper at >700 mphPenetrating injuries; burns through PPE not rated for the energy level
Intense lightUV/IR radiationArc eye (welder's flash), permanent retinal damage, temporary blindness
Sound>165 dBPermanent hearing loss; vestibular damage
⚡ Burns Begin at 1.2 cal/cm²
The threshold for a second-degree burn to unprotected skin is 1.2 calories per square centimeter (cal/cm²). An arc flash at a 480V motor control center can produce incident energies of 8–40 cal/cm² at working distance. Without arc-rated PPE, exposure at these levels is fatal.

NFPA 70E Arc Flash Approach Boundaries

BoundaryDescriptionWho May Cross
Flash Protection Boundary Outer limit — an unprotected person could receive a curable burn (just at 1.2 cal/cm²) if an arc occurred Nobody without PPE rated for the arc flash hazard
Arc Flash Boundary Distance within which a worker could receive a second-degree burn (≥1.2 cal/cm²) if an arc occurred QEP with arc-rated PPE only
Limited Approach Boundary Shock protection boundary — unqualified personnel must stop at this line QEP only (non-QEP may enter only with escort by QEP and appropriate PPE)
Restricted Approach Boundary Closest to the energized conductor — same risk as touching a conductor ("arc-in-a-box"); accidental contact likely QEP with full PPE and insulated tools only

PPE Categories — NFPA 70E Table 130.7(C)(15)(c)

CATIncident EnergyMinimum PPE RequiredTypical Scenario
CAT 0 < 1.2 cal/cm² Safety glasses, hearing protection, FR (flame-resistant) shirt, leather work gloves Low-voltage panels, 120V circuits
CAT 1 1.2 – 4 cal/cm² CAT 0 + arc-rated FR shirt and pants (4 cal/cm² rating), face shield, hard hat 240V residential/commercial panels
CAT 2 4 – 8 cal/cm² CAT 1 + arc-rated FR jacket, arc flash face shield hood (8 cal/cm²), Class 0 rubber gloves 480V motor control center (MCC)
CAT 3 8 – 25 cal/cm² 25 cal/cm² arc flash suit, arc flash hood, hearing protection, Class 2 rubber gloves 480V switchgear, industrial distribution
CAT 4 25 – 40 cal/cm² 40 cal/cm² arc flash suit, full arc flash hood, leather gloves over Class 2 rubber, hearing protection Medium voltage switchgear (4–15kV)
ℹ How to Read an Arc Flash Label

All electrical equipment at LEO job sites must be labeled with arc flash analysis data. A label will show: Nominal Voltage, Arc Flash Boundary distance (in inches or feet), Incident Energy (in cal/cm²), Required PPE Category, and Working Distance assumption. Never open a panel that lacks an arc flash label without first consulting QEP and performing a hazard assessment.

§07

Electrical PPE

The 6 Electrical PPE Items

PPE ItemStandardWhen RequiredLEO Rule
Insulating rubber gloves (Class 00–4) ASTM D120 Any energized electrical work above 50V QEP required for use. Must be inspected for cuts/punctures and air-tested before every use. Leather protectors worn over gloves for mechanical protection.
Arc flash face shield / hood ANSI Z87.1 / NFPA 70E Work near energized conductors with arc flash risk Required for CAT 1 and above. CAT 2+ requires full arc flash hood — a face shield alone is insufficient.
FR (flame-resistant) clothing NFPA 70E / ASTM F1506 Any arc flash risk present Required for CAT 0 and above. Must be arc-rated (cal/cm² rating matching or exceeding the hazard). Do NOT wear synthetic fabrics (they melt).
Insulating mats and blankets ASTM D1048 Working near live bus bars or open energized enclosures QEP judgment call based on hazard assessment. Must be rated for the voltage class present.
Safety glasses ANSI Z87.1 Always in electrical work areas Mandatory. Must be side-shielded in electrical areas. Provide minimal arc flash protection — not a substitute for arc face shield.
Voltage-rated (VDE) tools IEC 60900 Any electrical work — energized or not Red-handled IEC 60900 rated tools only at LEO. Standard tools are not insulated and must not be used for electrical work. Never use tools with damaged insulation.

Rubber Glove Classes — Voltage Ratings

ClassMax AC Proof VoltageMax Working Voltage ACColor Code
Class 002,500V AC500V ACBeige
Class 05,000V AC1,000V ACRed
Class 110,000V AC7,500V ACWhite
Class 220,000V AC17,000V ACYellow
Class 330,000V AC26,500V ACGreen
Class 440,000V AC36,000V ACOrange
⚠ Rubber Glove Inspection — Every Use

Before every use: (1) Visual inspection — look for cuts, abrasions, punctures, ozone cracking, embedded contaminants. (2) Roll-down air test — roll the cuff to trap air inside, squeeze to pressurize, check for leaks. (3) Check date stamp — rubber gloves must be tested every 6 months per ASTM D120 and are stamped with a test date. Never use expired or damaged gloves.

§08

Test Before Touch — Interactive Protocol Tool

The "test before touch" rule applies any time you are about to make contact with a terminal, conductor, or electrical component — even after LOTO has been applied. The three-step meter verification protocol (test-test-test) ensures that your measuring instrument is working before and after you use it.

⚡ Why Three Tests?
A meter can fail silently — a dead battery, a blown fuse on the meter, or a damaged lead can cause the meter to read zero on a live circuit. If you test a live source before and after testing your target, you know the meter was working for the entire sequence. Skipping step 1 or step 3 eliminates this safety net.

Scenario: Pre-Contact Verification

You are about to connect a meter to a terminal block that should be de-energized under LOTO. Click the steps in the correct order to complete the test-before-touch protocol.

✅ Correct! Test-Test-Test protocol completed. Your sequence: LOTO verification → Lead inspection → Known live test → Target test → Known live confirmation. This is the only sequence that guarantees both your meter and the circuit are verified.
❌ Incorrect sequence detected. The correct order is: (1) Verify LOTO, (2) Inspect leads, (3) Test known live source, (4) Test the target circuit, (5) Test known live source again. Never skip the verification steps — a silent meter failure can lead to fatal contact with a live conductor.
§09

Common Electrical Hazards in Industrial Settings

HazardDescriptionPrevention
Overhead power lines Often uninsulated distribution lines operating at 4–25kV. The most common cause of fatal electrocution in construction and industrial outdoor work. Maintain minimum 10-foot clearance for lines up to 50kV. A spotter is required when working equipment (cranes, lifts, ladders) near overhead lines. Call the utility before digging or lifting near lines.
Damaged extension cords Cracked insulation, cut cords, and damaged plugs expose conductors and create shock and fire hazards. Common in industrial environments due to mechanical damage. GFCI protection required for all outdoor and wet-area use. Inspect cords before every use. Never use a cord with exposed conductors, damaged insulation, or a missing ground pin. Remove from service immediately — do not tape over damage.
Improper or missing grounding Equipment grounding conductors (EGC) provide the fault-current return path that trips breakers during a ground fault. Without grounding, the equipment enclosure becomes energized and shock occurs on contact. Verify ground continuity before energizing any portable equipment. Use a three-wire (grounded) receptacle tester. Never remove or bypass the ground pin of a plug.
Overloaded circuits Circuits loaded beyond their ampacity cause overheating of conductors and insulation. Overheated insulation fails and creates ground faults or fires. Breakers that repeatedly trip are signaling an overloaded circuit. Match load to circuit ampacity. Do not bypass OCPs (overcurrent protection) or install higher-rated fuses to "fix" a tripping breaker. Never tape breakers in the ON position — this is a code violation and fire hazard.
Wet conditions Water reduces skin resistance from ~100,000Ω to ~1,000Ω, dramatically increasing the current from a given voltage. Standing water provides a low-resistance path to ground. GFCI protection is mandatory in wet and damp locations. No electrical work should be performed while standing in water. Ensure hands are dry before operating electrical controls.
Working alone If a worker suffers an electrical shock with no one present, there is no one to call 911, no one to de-energize the source, and no one to start CPR. Alone + electrocuted = death. Buddy system required for all electrical work at LEO. If a worker cannot be released from grip (muscle lock-up from current), the buddy can de-energize the source rather than trying to pull them free.
Capacitor discharge hazard Capacitors in power supplies, VFDs, motor drives, and UPS systems store electrical energy and retain charge after the main power is removed. A 480V VFD bus capacitor can hold lethal voltage for 5–15 minutes after shutdown. Follow manufacturer's discharge procedure. Wait the specified minimum time (commonly 5 minutes). Always verify with a meter — never assume discharge is complete because the indicator lights are off.
Back-fed circuits A circuit that appears de-energized at its primary breaker can be energized by a secondary source: a second transformer, a transfer switch, a generator, or a cross-connected neutral. Common in buildings with emergency power systems. Review the single-line diagram for all energy sources before isolating. Apply LOTO at all sources. Never assume a circuit is dead because one breaker is open. Always test before touch.
§10

Emergency Response — Electrical Incident

☠ CRITICAL — DO NOT TOUCH A VICTIM IN CONTACT WITH AN ENERGIZED SOURCE

If you grab a person who is being electrocuted, you will also be electrocuted. You become a second victim. The current that is killing them will flow through you. Your first priority is to break the electrical circuit — not to grab the victim.

Electrical Incident Response — Step by Step

1
DO NOT TOUCH — Assess Contact Status

Determine if the victim is still in contact with the energized source. Look for the source of power. Call out to them — do not run in and grab. If there is any possibility of contact with an energized source, treat them as still connected.

2
De-Energize the Source — If Safe to Do So

Throw the nearest circuit breaker, pull the disconnect, or push the E-stop. Use one hand only (keeps current from crossing your chest if you accidentally contact voltage). Use insulated tools. Look away from the panel when you operate the switch — arc flash can occur. Do this from the side, not from directly in front.

3
Call 911 Immediately

All electrical injuries require emergency medical evaluation. Even if the victim appears uninjured and is conscious, cardiac monitoring is required for a minimum of 24 hours after electrical contact. Cardiac arrhythmias can occur hours after the event. Do not let a victim "walk it off."

4
Begin CPR — Only After Source Is De-Energized and Victim Is Free

Verify the source is de-energized before approaching the victim. Once confirmed safe, begin CPR if the victim is unresponsive and not breathing. Continue until EMS arrives. Use an AED if available — electrical shock frequently causes ventricular fibrillation, which AEDs are designed to treat.

5
Treat Burns Conservatively

Cover electrical burns with clean, dry dressing. Do not apply ice, water, or creams to electrical burns. Electrical burns are frequently much deeper than they appear on the surface — internal tissue damage can be severe even when the skin wound looks minor. Inform EMS of entry and exit wound locations.

6
Notify LEO Supervisor — Initiate Incident Report

Contact your LEO supervisor immediately. Do not disturb the scene unless necessary for rescue. Document conditions: what equipment was involved, what work was being performed, whether LOTO was in place, presence of witnesses. An OSHA-recordable incident investigation will follow.

⚠ What NOT to Do in an Electrical Emergency
§11

Hazard Recognition — Interactive Scenarios

Read each scenario. Identify the primary electrical hazard present. Click your answer for immediate feedback.

Scenario 1 — The Door Cord
A heavy-duty extension cord is running from a wall outlet, under a metal fire door, and connecting to a power tool in the next room. The door closes on the cord repeatedly during the day. What is the primary electrical hazard?
Scenario 2 — Panel Access
A worker just washed their hands and, without drying them, opens a 480V motor control center (MCC) panel to reset a tripped overload relay. Their hands are visibly wet. What is the primary hazard?
Scenario 3 — Taped Breakers
During a walkthrough of an electrical room, you observe two circuit breakers in a lighting panel that have been taped in the ON position. A sticky note reads "Do not trip — HVAC unit." What is the primary hazard?
Scenario 4 — The Modified Plug
A power tool is connected to an extension cord via a standard three-prong plug. On closer inspection, the round ground prong has been cut off, presumably to fit a two-prong outlet. What hazard does this create?
Scenario 5 — Overhead Work
A technician is on a step ladder performing roof-edge inspection. The top of the ladder is approximately 8 feet from an uninsulated overhead distribution line. The line is assumed to be 13.8kV from the utility. Is the technician safe at this distance?
§12

OSHA Regulations — Electrical Safety Reference

StandardTitleKey Requirements for LEO Technicians
29 CFR 1910.147 Control of Hazardous Energy (Lockout/Tagout) Written LOTO program required; all energy sources identified and controlled; employee training; periodic inspections; personal lock requirement; energy verification before work begins
29 CFR 1910.303 General Electrical — Wiring Design and Protection Working clearances in front of electrical panels (min. 3 ft for 120–250V, increasing with voltage); guarding of live parts; proper wiring methods; equipment ratings matching the installation
29 CFR 1910.305 General Electrical — Wiring Methods, Components, and Equipment Extension cord limitations (not as permanent wiring); GFCI requirements for temporary power; cord condition requirements; strain relief; ampacity matching
29 CFR 1910.333 Electrical — Safe Work Practices (Energized Work) Energized work permit requirements; approach distance tables; one-hand rule for panel switching; insulated tools and PPE; qualified worker definition; two-person rule
29 CFR 1910.335 Safeguards for Personnel Protection Required PPE for electrical work; insulating protective equipment; non-conductive headgear; face protection; inspection and testing of PPE; prohibited clothing (synthetic fabrics, conductive jewelry)
NFPA 70E (2024) Standard for Electrical Safety in the Workplace Arc flash risk assessment methodology; PPE categories (CAT 0–4); incident energy analysis; approach boundary definitions; energized electrical work permits; shock and arc flash hazard identification
ℹ OSHA vs. NFPA 70E

OSHA 29 CFR 1910 Subpart S is the regulatory requirement enforced by law. NFPA 70E is a consensus standard developed by industry experts that provides detailed technical guidance on how to comply with OSHA's requirements, particularly for arc flash. OSHA cites NFPA 70E as the authoritative source for arc flash PPE requirements. Both must be followed.

§13

Knowledge Assessment

Answer all 5 questions. A score of 4/5 (80%) or higher is required to complete this lesson. Select your answer and click Check.

Q1 — A technician is accidentally exposed to 250 mA of current flowing through their body. What is the most likely physiological outcome?
Q2 — Before touching any electrical terminal — even after LOTO has been applied and the circuit has been de-energized — you must:
Q3 — A non-QEP L2 technician discovers an open junction box with exposed 480V wiring while cleaning a pump room. The junction box cover is missing and conductors are visible. What is the correct action?
Q4 — An arc flash label on a switchgear panel indicates the Arc Flash Boundary is at 8 feet from the front of the panel. An unqualified (non-QEP) worker needs to get to 6 feet to read the equipment nameplate. What must happen?
Q5 — A worker with wet skin (resistance ≈ 1,000Ω) makes accidental contact with a 480V conductor. Using Ohm's Law (I = V ÷ R), what is the approximate current flowing through their body?
§14

Field Safety Checklist — Electrical Safety Awareness

Click each item to mark it complete. Use before beginning any work in an area with electrical equipment present.

← 4.15 Mechanical Troubleshooting Patterns LEO Technical Academy 5.2 Principles of DC →